| Application |
BS5308 cables are used to
carry voice and data services, they also serve as the interconnection
between electrical equipment and instruments, particularly in
and around process plants, where transducer generated signals
are transmitted through to panels, controllers and other devices. |
| Standards |
BS5308 Part 1 Polyethylene Insulated Conductors |
| Conductor |
Plain annealed copper conductors complying
with BS6360 |
| Construction conductors |
Plain annealed copper conductors complying
with BS6360 |
| Insulation |
Polyethylene to BS6234 type 03 or XLPE
(Cross Linked Polyethylene) for LSZH cables. (LSZH cables are
generally to BS5308) |
| Pairing |
Two insulated conductors uniformly twisted
together with a lay not exceeding 100mm. |
| Pair identification - individually pair
screened cables |
One blue core and one black core in each
pair identified by a numbered pair screen isolation tape. (Collectively
Screened Pairs) Coloured, as per BS5308 PT1 |
| Pair screens - individually screened pairs |
Where individual pair screening is required,
an Aluminium/Polyester tape screen is applied to each pair,
Metallic side down and in continuous contact with a 0.5mm²
tinned copper drain wire |
| Pair screens - collectively screened cables |
For cables requiring a collective screen,
an Aluminium/Polyester tape screen is applied over the laid
up pairs metallic side down and in continuous contact with a
0.5mm² tinned copper drain wire. |
| Outer protection |
| Type 1 |
Extruded flame retardant
PVC sheath (BS7655 Type TM1 or Type 6) or LSZH. |
| Type 2 |
Extruded polyethylene bedding (BS6234
Type 2C or 3C), Galvanised Steel wire armour (BS1442),
Extruded flame retardant PVC sheath (BS7655 Type TM1)
or LSZH. |
| Type 3 |
PVC bedding (BS7655 Type TM1 or
Type 6), Extruded sheath of Lead Alloy (BS801), Galvanised
Steel Wire Armour (BS1442), PVC sheath (BS7655 Type TM1). |
|
| Standard sheath colours |
Blue and Black. |
| Note: |
These cables are not suitable for direct
connection to the public mains supply. |
| Voltage Rating |
300/500V |
| Temperature Rating |
0 to +70°C |
| Minimum Bending Radius |
10 x overall diameter |
| Eland Product Group Ref |
A3I |
|
| Application: |
BS5308 cables are used to carry voice
and data services, they also serve as the interconnection between
electrical equipment and instruments, particularly in and around
process plants, where transducer generated signals are transmitted
through to panels, controllers and other devices. |
| Standards |
BS5308 Part 2 PVC Insulated Conductors |
| Conductor |
Plain annealed copper conductors complying
with BS6360 |
| Construction conductors |
Plain annealed copper conductors complying
with BS6360 |
| Insulation |
PVC to BS6746 type TI 1 |
| Pairing |
Two insulated conductors uniformly twisted
together with a lay not exceeding 100mm. |
| Pair identification - individually pair
screened Cables |
One blue core and one black core in each
pair identified by a numbered pair screen isolation tape. (Collectively
Screened Pairs) Coloured as per BS5308 PT2 |
| Pair screens - individually screened pairs |
Where individual pair screening is required,
an Aluminium/Polyester tape screen is applied to each pair,
Metallic side down and in continuous contact with a 0.5mm²
tinned copper drain wire |
| Pair screens - collectively screened cables |
For cables requiring a collective screen,
an Aluminium/Polyester tape screen is applied over the laid
up pairs metallic side down and in continuous contact with a
0.5mm² tinned copper drain wire. |
| Outer Protection |
| Type 1: |
Extruded flame retardant PVC sheath (BS7655
Type TM1 or Type 6. |
| Type 2: |
Extruded PVC bedding (BS7655 Type TM1), Galvanised Steel
wire armour (BS1442), Extruded flame retardant PVC sheath
(BS7655 Type TM1) |
|
| Standard sheath colours |
Blue and Black. |
| Note: |
These cables are not suitable for direct
connection to the public mains supply. |
| Voltage Rating |
300/500V |
| Temperature Rating |
0 to +70°C |
| Minimum Bending Radius |
10 x overall diameter |
| Eland Product Group Ref |
A3I |
| Range of Instrumentation Cables |
| Conductor |
0.40 mm Dia (0.126 Sq. mm
to 2.502 Sq. mm) Electrolytic Copper Conductor Bare / Tinned,
Solid / Stranded |
| Insulation |
General Purpose / Heat Resistant 70"C
to 85"C PVC/ Polythene Compound Insulation |
| Elements |
Pairs/ Triads/ Quads. Colour coded / Number
printed |
| Shields |
Aluminum Polyester Tape Screen with Copper
drain wire or alternately with Copper wire braiding individual
element or overall shielding as specified. |
| Armouring |
Galvanized Steel wire / strip armour |
| Sheathing |
PVC 70"C / 90"C F.R.L.S / LSOH
compound as per Customer requirement. |
| Operating Temperature |
70"C |
| Minimum Bending Radius |
8 X Overall Diameter |
| 300/500 V Voltage Grade 0.75
Sq. mm, Multi Pair/ Multi Triad, Copper Conductor, PVC Insulated,
Twisted, Individual & Overall Screened with AI. Mylar Tape,
GI Wire Armoured, PVC Sheathed Instrumentation Cables. |
Physical
Parameters for Signal / Instrumentation Cables (as per BS
; 5308) (II) |
| No. of Paris/ Triads |
Insulation Thickness mm (Nom) |
Inner Sheath Thickness mm (Nom) |
Armour Size mm (Nom) |
Outer Sheath Diameter mm Appx. |
Overall Diameter mm Appx. |
Approx. Weight. (Kg/Km) |
1P |
0.60 |
0.80 |
0.90 |
1.40 |
11.80 |
270.00 |
6P |
0.60 |
1.20 |
1.25 |
1.60 |
21.8 |
890.00 |
12P |
0.60 |
1.30 |
1.60 |
1.80 |
28.30 |
1500.00 |
1T |
0.60 |
0.80 |
0.90 |
1.40 |
12.00 |
290.00 |
4T |
0.60 |
1.20 |
1.25 |
1.60 |
21.6 |
850.00 |
8T |
0.60 |
1.30 |
1.60 |
1.80 |
28.30 |
1460.00 |
| 300/500 V Voltage Grade 1.50Sq.
mm, Multi Pair/ Multi Triad, Copper Conductor, PVC Insulated,
Twisted, Individual & Overall Screened with AI. Mylar Tape,
GI Wire Armoured, PVC Sheathed Instrumentation Cables. |